TSXCAY33
Schneider Electric
Overview
The TSXCAY33 is a Motion control modules in the Modicon Premium Automation platform range from Schneider Electric. It is engineered for industrial automation duties within the Modicon Premium / TSX ecosystem.
Application & Technical Notes
As a motion control modules, the TSXCAY33 is intended for deployment in panel-based control cabinets and machine enclosures where Modicon Premium / TSX equipment is installed. It performs a defined automation function within the control system and is selected to match the installed Schneider Electric platform.
Key published characteristics include a 24 V DC reflex output: rating, an operating temperature range of 32…140 °F (0…60 °C). These values should be confirmed against the current manufacturer datasheet before final selection, as options and suffixes vary by configuration.
Maintenance & Diagnostics
Respect the published operating temperature window (32…140 °F (0…60 °C)); do not exceed it during commissioning or in enclosed panels without airflow. For storage and transit, keep the unit within -13…158 °F (-25…70 °C). Avoid condensation — the rated humidity is 5…95 % without condensation; store and operate the module in a dry, pollution-degree-appropriate enclosure. Verify field wiring, shielding and grounding at installation; check terminal torque and confirm signal types match the configured range. Periodically inspect for loose terminations, induced noise and channel-level diagnostics reported by the controller. Always de-energise the circuit and follow lock-out/tag-out before handling; refer to the official instruction bulletin for service procedures.
Sourcing & Procurement
When sourcing the TSXCAY33, distinguish three supply tiers: (1) genuine Schneider Electric stock from an authorised distributor; (2) compatible equivalents or surplus/NOS (new-old-stock) from third parties; (3) alternative parts offering equivalent function. Genuine supply carries the full warranty and traceability; compatible or alternative items may be cheaper but should be validated for form, fit, firmware and certification before use in a live system. PLCXpert publishes this page as an independent reference and does not sell the part — verify every claim with the manufacturer or your distributor.
Confirm the module matches your Modicon Premium / TSX rack, the required channel count, signal type and voltage, and the firmware/configuration of the controller. Lead times and pricing vary by region and lifecycle status; obtain a current quote from an authorised channel rather than relying on stale listings.
Frequently Asked Questions
What is the TSXCAY33?
The TSXCAY33 is a motion control modules in the Modicon Premium Automation platform range from Schneider Electric. It is described by the manufacturer as: Motion control modules.
What are the key technical ratings of the TSXCAY33?
Its published highlights include 24 V DC reflex output:, operating temperature 32…140 °F (0…60 °C). Full electrical, mechanical and environmental limits are listed in the manufacturer datasheet and should be confirmed for your exact suffix.
How is the TSXCAY33 mounted or installed?
Installation follows the standard Modicon Premium / TSX mounting practice for this device class; refer to the installation manual for exact dimensions and torque.
Is the TSXCAY33 compatible with my controller?
It is part of the Modicon Premium / TSX family. Confirm the specific rack, firmware revision, slot rules and configuration with the controller documentation before purchase, as compatibility depends on the exact system build.
What should I check before buying the TSXCAY33?
Verify the genuine part number and suffix, confirm it matches your platform and ratings, check the current lifecycle/availability status, and buy from an authorised distributor. PLCXpert provides this reference only and does not sell the component.
Specifications
The TSXCAY33 is a specialized motion control module from Schneider Electric's TSX Micro PLCs series, tailored for servo motors. This unit is designed for precise operational control and accommodates various input configurations.
Complementary
| Note | Speed profile path Trapezoidal or parabolic Resolution <= 1000 position units per point >= 0.5 position units per point Length of axis 256…32000000 P Acquisition speed >= 54000 points/mn <= 270000 points/mn Acceleration time 8 ms...10 s Operating mode Direct drive mode FOLLOWER Automatic Manual OFF Type of axis Limited axis 2/3 axis linear interpolation I/O modularity 3 axes |
|---|---|
| Input compatibility | N/A |
| Incremental encoder 10...30 V totem pole | Incremental encoder 5 V DC RS422 With 2-wire/3-wire sensor (24 DC) auxiliary input Absolute encoder parallel output ABE7CPA11 Absolute encoder SSI output 12...25 bits |
| Clock frequency | 200 kHz SSI absolute encoder Incremental encoder frequency x1 500 kHz Incremental encoder frequency x 4 1000 kHz in counting 250 kHz in input |
| Power dissipation in W | 10…17 W |
| Input type | Current sink auxiliary input EN/IEC 1131 Type 2 Resistive servo drive control input EN/IEC 1131 Type 1 Resistive counter input |
| Input logic | Positive |
| Input voltage | 24 V 8 mA auxiliary input 24 V 8 mA servo drive control input 5 V 18 mA counter input |
| Input voltage limits | <= 5.5 V counter input 19...30 V auxiliary input 19...30 V servo drive control input |
| Voltage state 1 guaranteed | >= 11 V auxiliary input >= 11 V servo drive control input >= 2.4 V counter input |
| Current state 1 guaranteed | >= 3.5 mA servo drive control input) >= 3.7 mA counter input) >= 6 mA auxiliary input) |
| Voltage state 0 guaranteed | <= 1.2 V auxiliary input <= 1.2 V counter input <= 5 V servo drive control input |
| Current state 0 guaranteed | <= 1 mA counter input) <= 1.5 mA servo drive control input) <= 1 mA auxiliary input) |
| Input impedance | 270 Ohm counter input 3000 Ohm auxiliary input 3000 Ohm servo drive control input Number of outputs 3 reflex output static EN/IEC 61131 3 analogue output static 3 servo drive validation output relay |
| Analogue output range | +/- 10...24 V Analogue output resolution 13 bits + sign LSB value 1.25 mV analogue output |
| Output voltage | 24 V DC reflex output: 24 V DC servo drive validation output: |
| Output voltage limits | Reflex output 19...30 V Servo drive validation output 5...30 V |
| Nominal output current | 0.5 A reflex output Maximum output current 1.5 mA analogue output 200 mA servo drive validation output 625 mA reflex output Minimum load 1 mA 1 V |
| Maximum voltage drop | <1 V at state on reflex output |
| Maximum leakage current | 0.3 mA reflex output |
| Switching time | < 5 ms for servo drive validation < 500 µs for reflex output |
| Output compatibility | Positive logic DC inputs (resistance <= 15 kOhm) reflex |
| Short-circuit protection | Current limiter reflex output Thermal tripping reflex output |
| Output overload protection | Current limiter reflex output Thermal tripping reflex output |
| Output overvoltage protection | Zener diode between outputs and 24 DC reflex output |
| Reverse polarity protection | Reflex output reverse diode on supply |
| Local signalling | 1 LED (green) for module operating (RUN) 1 LED (red) for external fault (I/O) 1 LED (red) for internal fault, module failure (ERR) 3 LEDs (green) for axis diagnostics available |
| Electrical connection | 1 connector HE-10 20 pins for servo drive ctrl inputs + for ext power supply of servo drive inputs/outputs 2 connectors HE-10 20 pins for aux inputs, reflex output, for external sensor and preactuator power supply 1 connector SUB-D 9 for an analogue output (speed reference) 3 connectors SUB-D 15 for an incremental or absolute encoder |
| Current consumption | 22...40 mA 24 V DC on 10/30 V absolute encoder module 1500 mA 5 V DC 30 mA 24 V DC |
| Module format | Double |
| Net weight | 1.34 lb(US) (0.61 kg) |
Environment
| Protective treatment | TC |
|---|---|
| Ambient air temperature for operation | 32…140 °F (0…60 °C) |
| Ambient air temperature for storage | -13…158 °F (-25…70 °C) |
| Relative humidity | 5…95 % without condensation |
| Operating altitude | <= 2000 m |
Description
| Note | The Schneider Electric TSXCAY33 stands as a versatile motion control module within the TSX Micro PLCs series, specifically for servo motor applications. The module adopts a standard format and is engineered to facilitate intricate motion operations. With the servo loop designed to be proportional to overshoot compensation and gain switching, the TSXCAY33 ensures highly responsive control. Users can select between trapezoidal or parabolic speed profiles tailored to their requirements. The resolution of this module is exceptional, supporting positions up to 1000 units per point and maintaining accuracy down to 0.5 position units. In terms of performance, the module demonstrates impressive acquisition speeds, reaching up to 270,000 points per minute, with a minimum rate of around 54,000 points per minute. Operating modes for the TSXCAY33 include OFF, FOLLOWER, Manual, Direct drive mode, and Automatic, providing flexible operational choices. It supports 2/3 axis linear interpolation, accommodating diverse motion applications. The TSXCAY33 also excels in input compatibility, integrating with various encoder types. These include absolute encoders with SSI output ranging from 12 to 25 bits and incremental encoders boasting voltages from 10-30 V totem pole configurations. Additional inputs for 2-wire/3-wire sensors and absolute encoders with ABE7CPA11 parallel output further enhance its capabilities. The clock frequency specification is noteworthy. It supports up to 200 kHz for SSI absolute encoders and higher frequencies for incremental encoders, allowing for detailed and rapid counting. Power dissipation for this module falls within the range of 10 to 17 W, ensuring efficient operation. The input voltage requirements are straightforward: 24 V for both auxiliary and servo drive control inputs and 5V for counter input operation. The current sink auxiliary input adheres to EN/IEC 1131 Type 2 standards, establishing reliable performance standards for resistive input applications. |
|---|
Reproduced from the manufacturer's published data. Values marked "Not available" are absent from the source document.