IS220PAOCH1A
GE
Overview
The IS220PAOCH1A is an Analog Output Module from GE. It provides Eight current output channels channels and is built for signal interfacing within the GE product portfolio systems.
Application & Technical Notes
As an analog output module, the IS220PAOCH1A is intended for deployment in panel-based control cabinets and machine enclosures where the GE product portfolio equipment is installed. It drives actuators, relays, valves and indicators from controller commands, acting as the actuation layer between logic and the machine.
Key published characteristics include Eight current output channels channels. These values should be confirmed against the current manufacturer datasheet before final selection, as options and suffixes vary by configuration.
Maintenance & Diagnostics
Verify field wiring, shielding and grounding at installation; check terminal torque and confirm signal types match the configured range. Periodically inspect for loose terminations, induced noise and channel-level diagnostics reported by the controller. Always de-energise the circuit and follow lock-out/tag-out before handling; refer to the official instruction bulletin for service procedures.
Sourcing & Procurement
When sourcing the IS220PAOCH1A, distinguish three supply tiers: (1) genuine GE stock from an authorised distributor; (2) compatible equivalents or surplus/NOS (new-old-stock) from third parties; (3) alternative parts offering equivalent function. Genuine supply carries the full warranty and traceability; compatible or alternative items may be cheaper but should be validated for form, fit, firmware and certification before use in a live system. PLCXpert publishes this page as an independent reference and does not sell the part — verify every claim with the manufacturer or your distributor.
Confirm the module matches your GE product portfolio rack, the required channel count, signal type and voltage, and the firmware/configuration of the controller. Lead times and pricing vary by region and lifecycle status; obtain a current quote from an authorised channel rather than relying on stale listings.
Check live stock, lead time and request a quote for IS220PAOCH1A (opens in a new tab)
Frequently Asked Questions
What is the IS220PAOCH1A?
The IS220PAOCH1A is an analog output module from GE. It is described by the manufacturer as: Analog Output Module.
What are the key technical ratings of the IS220PAOCH1A?
Its published highlights include Eight current output channels channels. Full electrical, mechanical and environmental limits are listed in the manufacturer datasheet and should be confirmed for your exact suffix.
How is the IS220PAOCH1A mounted or installed?
Installation follows the standard GE product portfolio mounting practice for this device class; refer to the installation manual for exact dimensions and torque.
Is the IS220PAOCH1A compatible with my controller?
It belongs to GE's automation product portfolio. Confirm the specific rack, firmware revision, slot rules and configuration with the controller documentation before purchase, as compatibility depends on the exact system build.
What should I check before buying the IS220PAOCH1A?
Verify the genuine part number and suffix, confirm it matches your platform and ratings, check the current lifecycle/availability status, and buy from an authorised distributor. PLCXpert provides this reference only and does not sell the component.
Specifications (source data)
SPECIFICATIONS
Part Number: IS220PAOCH1A Manufacturer: General Electric Series: Mark VIe Product Type: Analog Output Module Number of channels: Eight current output channels Analog Outputs: 0-20 mA, up to 900 Ω Accuracy: ±0.5% over -30 to 65oC (-22 to 149 oF) temperature Size: 8.26 cm high x 4.19 cm wide x 12.1 cm deep (3.25 in x 1.65 in x 4.78 in) Availability: In Stock Country of Origin: USA
IS220PAOCH1A is an Analog Output Module manufactured by General Electric as part of Mark VIe used in gas turbine control management systems. An electrical interface between one or two I/O Ethernet networks and an analog output terminal board is provided by the Analog Output (PAOC). A BPPx processor board and an acquisition board pair tailored to the analog output function are both present in the PAOC. Up to eight simplexes, 0-20 mA current loop outputs can be provided by the PAOC, which also has an analog to digital converter for each output's current feedback. Dual RJ-45 Ethernet connectors and a three-pin power input serve as the PAOC's inputs. The related terminal board connector is directly connected to the output via a DC-37 pin connector. Indicator LEDs are used to display visual diagnostics.
TBAO Analog Output Terminal Board
PAOC COMPATIBILITY:
One of the following BPPx processor boards is compatible with the PAOC I/O pack:
TBAOHIC Terminal Board
There is a BPPB processor board within the PAOCH1A. The controlST* Software Suite V04.06 and later supports the functionally compatible BPPC found in the PAOCH1B. Only the analog output terminal boards TBAOH1C and STAOH1A/H2A indicated in the accompanying table are compatible with the PAOC.
PAOC I/O PACK INSTALLATION: Mount the selected terminal board firmly. Directly connect the PAOC I/O pack(s) to the connector on the terminal board (s). Using the threaded studs next to the Ethernet ports, mechanically fasten the I/O pack(s). The studs slip into a mounting bracket made for the particular style of the terminal board. It is important to position the bracket such that the DC-37 pin connector connecting the I/O pack and the terminal board is not subjected to right-angle forces. In the course of the product's service life, the adjustment should only be necessary once. Depending on the setup of the machine, connect either one or two Ethernet wires. Either port will work with the I/O pack. If When using dual connections, it is customary to link ENET1 to the network connected to the R controller. Connect the connector on the side of the PAOC to provide power to the I/O pack. Because the I/O pack has an inherent soft-start feature that regulates current inrush on power application, it is not essential to turn off the power before plugging the cable in. If necessary, set up the I/O pack using the ToolboxST* program. Press F1 to bring up the Component Editor's help menu.
ANALOG OUTPUT HARDWARE:
Eight simplex 0-20 mA analog outputs with 18 V compliance are included in the PAOC. An external transistor amplifier is controlled and driven by a 16-bit digital-to-analog converter (DAC), which also controls the output current. To alert the control if the internal temperature of the pack becomes too high, a temperature sensor is built inside the board. Additionally, each analog output circuit has a mechanical normally-open relay that controls whether the output is enabled or disabled. When the disabled relay is turned off, the output flows via the relay and opens a circuit between the customer load attached to the terminal board and the analog output of the PAOC. The location of the mechanical relay is signaled by an LED using the second normally-open contact of the relay.
PAOC Analog Output Pack
CURRENT FEEDBACK HARDWARE:
For each of the eight simplexes 0-20 mA analog outputs, the PAOC includes current feedback monitoring. The output current is sensed and tracked using a 16-bit analog to digital converter and a 50 resistor on the terminal board. Analog Digital Converter
The PAOC I/O pack, which has eight linear, high-compliance analog outputs, has application restrictions based on its probable ambient environment. As measured from the outside of the pack, PAOCH1B packs are designed to operate within a temperature range of -40 to 70 oC (-40 to 158 oF). Due to its dense triple board layout and depending on the application, the PAOC's ambient environment maximum must be reduced. Here is a list of output configurations along with the necessary de-ratings for each one. As evidenced by the terminal board screws across the output range of 0–20 mA, the minimum series equivalent resistance of the customer load is the definition of the minimum output impedance.
The PAOC I/O pack performs the following self-diagnostic tests:
A power-up self-test that examines the hardware on the processor board, Ethernet ports, RAM, and flash memory.
Constantly checking if the internal power supply is operating properly Verifying that the hardware set matches by comparing the electronic ID data from the CPU, acquisition, and terminal boards, then checking that the application code loaded from flash memory is appropriate for the hardware set. A modest burden resistor is used on the terminal board to sense the analog output current. To verify the circuits in the digital to the analog converter are functioning properly, the I/O pack conditions this signal and compares it to the commanded current. The analog output suicide relay's compliance with the commanded condition and feedback indication is continuously checked.
PAOC SPECIFIC ALARAMS
POSSIBLE CAUSE:
The valid output range of the analog output is being exceeded. Out-of-range feedback on the analog output. A pack or terminal board hardware malfunction may have occurred. SOLUTIONS:
Ensure that the analog output command is between 0 and 20 milliamps (mA). Check to see if the analog output feedback agrees with the anticipated command. Check the field wiring and connectors for analog outputs. A board failure is likely if all active analog output feedbacks are unhealthy with valid instruction. Replace the terminal board and I/O pack.